Selectable pump alternation when used with two pumps to minimize pump wear. With alternation "on" a seal failure or over temperature condition will force the non-failed pump to lead status and stop alternation. When used with a submersible pump including a moisture sensor the MPC has alarm light indication of seal failure.
Selectable pump alternation when used with two pumps to minimize pump wear. With alternation "on" a seal failure or over temperature condition will force the non-failed pump to lead status and stop alternation. When used with a submersible pump including a moisture sensor the MPC has alarm light indication of seal failure.
Versatile level control in a standard ¼ DIN package, this controller features two additional programmable alarm contacts and a front panel button that displays pump run time. Minimize pump wear with selectable pump alternation and time delay for pump two upon power up. In addition, this controller displays the present level and primary set point value.
Features
Applications
Inputs | 4 (or 0) to 20 mA DC |
Input Impedance | Current = 10 Ω |
Output Ratings | Control relays: SPDT, rated 10 A at 240 V AC resistive, ¼ hp at 120 V AC, ⅓ hp at 240 V AC Alarm relays: SPST, 3 A at 240 V AC resistive, 1⁄10 hp at 120 V AC |
Control Type | On/off, reverse (pump out) or direct (pump in) acting |
Accuracy | ±0.25% of span, ±1 least significant digit |
Display | Two 4 digit, 7 segment 0.56" (14.224 mm) high LEDs Resolution: 1 count |
Memory Backup | Nonvolatile memory (no batteries required) |
Ambient Operating Temperature/RH | 14 to 131°F (-10 to 55°C)/0 to 90% up to 104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) non-condensing |
Loop Power Supply (Isolated) | 24 V DC at 50 mA, regulated |
Seal Failure (Moisture Sensor) | Power: 2.5 V DC Search current: 3 μA Resolution: 10 K to 500 KΩ in 10 KΩ steps |
Power | Requirements: 100 to 240 V AC nominal, 10 to 15%, 50 to 400 Hz, single phase; 132 to 240 V DC nominal, 10 to 15% Consumption: 7.5 VA maximum |
Front Panel Rating | Meets UL Type 4X (IP66) |
Agency Approvals | cULus |
Dimensions | 3.78 x 3.78 x 4.5" (95.9 x 95.9 x 114.3 mm) |
Weight | 16 oz (454 g) |
Inputs | 4 (or 0) to 20 mA DC |
Input Impedance | Current = 10 Ω |
Output Ratings | Control relays: SPDT, rated 10 A at 240 V AC resistive, ¼ hp at 120 V AC, ⅓ hp at 240 V AC Alarm relays: SPST, 3 A at 240 V AC resistive, 1⁄10 hp at 120 V AC |
Control Type | On/off, reverse (pump out) or direct (pump in) acting |
Accuracy | ±0.25% of span, ±1 least significant digit |
Display | Two 4 digit, 7 segment 0.56" (14.224 mm) high LEDs Resolution: 1 count |
Memory Backup | Nonvolatile memory (no batteries required) |
Ambient Operating Temperature/RH | 14 to 131°F (-10 to 55°C)/0 to 90% up to 104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) non-condensing |
Loop Power Supply (Isolated) | 24 V DC at 50 mA, regulated |
Seal Failure (Moisture Sensor) | Power: 2.5 V DC Search current: 3 μA Resolution: 10 K to 500 KΩ in 10 KΩ steps |
Power | Requirements: 100 to 240 V AC nominal, 10 to 15%, 50 to 400 Hz, single phase; 132 to 240 V DC nominal, 10 to 15% Consumption: 7.5 VA maximum |
Front Panel Rating | Meets UL Type 4X (IP66) |
Agency Approvals | cULus |
Dimensions | 3.78 x 3.78 x 4.5" (95.9 x 95.9 x 114.3 mm) |
Weight | 16 oz (454 g) |