Veris E30A042 Panelboard Monitoring System, Power and Current for One 3-Phase Main, Advanced

Model: E30A042

Veris E30A042 Panelboard Monitoring System, Power and Current for One 3-Phase Main, Advanced

Model: E30A042

Advanced Monitoring - Power and Current for one 3-phase main, one neutral, and 42 branch circuits, 100 Amp CT with 3/4" spacing, 2 CT strips, Modbus communications, 90 to 277V AC (L-N).

Advanced Monitoring - Power and Current for one 3-phase main, one neutral, and 42 branch circuits, 100 Amp CT with 3/4" spacing, 2 CT strips, Modbus communications, 90 to 277V AC (L-N).

Sale Price $4471.42 USD
Regular Price $4996.00 USD
Availability 2 to 3 Weeks
Quantity

VERIS E30A042 Solid Core Panelboard Monitoring System

The E30 Solid-Core Panelboard Monitoring System is the ideal device for electrical load management. This model includes the advanced unit with a 100A, 3/4 inch spacing CT option, and 2 strips of 21 CTs with two 4 ft. flat ribbon cables. This device is capable of monitoring currents of 1/4 A to 100 A on up to 92 circuits (84 branch circuits, two three-phase mains, and two neutrals). The E30 has a sampling frequency of 2560Hz, an overload capability of 22kAIC, and an input power of 90 to 277VAC, 50/60Hz. The user configurable thresholds trigger alarm indicators when any circuit approaches the threshold, preventing overload. Data updates occur every 1.8 seconds, providing you with up-to-date information vital to overload prevention. Recorded data may be easily transferred to a local PC via the Modbus RTU networked connection.

Features

  • IEC Class 1 metering accuracy
  • Up to 126 panelboards can be monitored on one RS-485 drop...simplifies wiring
  • Reports voltage, current, power and energy for mains and branches...one product covers the whole panelboard
  • Monitors up to 46 circuits (42 branch circuits, one 3-phase main, one neutral) with one device...saves space
  • 3/4" spaced solid-core 100 A current sensors…flexible installation
  • 4 user-configurable alarm threshold registers and individual monitoring of all branches...improved load management
  • Built-in ability to set the orientation and numbering of the circuits
  • 1/4 A to 100 A monitoring...widest dynamic range in the industry
  • Flexible installation options - can use ribbon cables from 18" (0.46 m to 20 ft (6 m)
  • Versatile support for any combination of 1, 2, 3 pole breakers

Applications

Ideal for the following applications: Branch Circuit Monitoring in New Construction, Load Based Cost Allocation, Overload Protection, Load Management, Load Balancing and Lighting Circuits.

Key Features

  • Revenue Grade measurements
  • IEC Class 1 metering accuracy
  • Up to 126 panelboards can be monitored on one RS-485 drop...simplifies wiring
  • Reports volts, amps, power, and energy for each circuit...one product covers the whole panelboard
  • 92 circuits with one product (84 branch circuits, 2 3-phase mains, 2 neutrals)... saves space
  • 3/4", or 1", or 18 mm spaced solid-core current sensors...flexible installation
  • Split-core version has two mounting options (DIN Rail or Snaptrack)... installation flexibility
  • 4 user-configurable alarm threshold registers...improved load management
  • Built-in ability to set the orientation and numbering of the circuits
  • 1/4 amp to 100 amp solid-core monitoring...widest dynamic range in the industry
  • 1, 2, 3 pole breaker support
  • Applications for new construction (solid-core version) and retrofits (split-core version)
  • Modbus RTU standard
  • Modbus TCP over Ethernet available with addition of U013-0012...page 166
  • BACnet IP or MS/TP available with addition of E8950...see page 164 (E30Ax84 and E31Axxx not supported)

Specifications

Inputs:
  • Input Power 90-277 VAC, 50/60 Hz
Accuracy:
  • Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
  • Voltage ±0.5% of reading 90-277 V line-to-neutral
Operation:
  • Sampling Frequency 2560 Hz
  • Update Rate 1.8 s
  • Overload Capability 22 kAIC
Network Communications:
  • Type Modbus® RTU
  • Connection DIP switch-selectable 2-wire or 4-wire, RS-485
  • Address DIP switch-selectable address 1 to 247 (pairs of 2)
  • Baud Rate DIP switch-selectable 9600, 19200, 38400
  • Parity DIP switch-selectable NONE, ODD, EVEN
  • Communication Format 8 data-bits, 1 start-bit, 1 stop-bit
Mechanical:
  • Ribbon Cable Support 2 ea 4 ft. (0.9 m) flat ribbon cables ship standard; up to 20 ft. (6 m) available
Environmental:
  • Operating Temperature 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
  • Storage Temperature -40° to 70°C (-40° to 158°F)
Safety:
  • UL508, EN61010
Click here for complete specifications on the Veris E30A042

Veris E30A042 Specifications

Input Power 90-277 VAC, 50/60 Hz
Power Energy IEC 62053-21 Class 1, ANSI C12.1-2008
Sampling Frequency 2560 Hz
Update Rate 1.8 s
Overload Capacity 22 kAIC
Click here for complete specifications on the Veris E30A042

What's included with the Veris E30A042

  • E30A042 Advanced Main Circuit Board
  • 2 x Strips of 21 ea 100 A Solid Core Current Transducers Spaced 3/4" Apart
  • 2 x 4ft Flat Ribbon Cables

Veris E30 Series Comparison

Monitoring at Mains E30A E30B E30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage, L-L and average
Voltage, L-N and average
Voltage, L-N and per phase
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under

* Based on a 3-phase breaker rotation.

Ask a question about Veris E30A042 Panelboard Monitoring System, Power and Current for One 3-Phase Main, Advanced

Customer Reviews for the Veris E30A042

VERIS E30A042 Solid Core Panelboard Monitoring System

The E30 Solid-Core Panelboard Monitoring System is the ideal device for electrical load management. This model includes the advanced unit with a 100A, 3/4 inch spacing CT option, and 2 strips of 21 CTs with two 4 ft. flat ribbon cables. This device is capable of monitoring currents of 1/4 A to 100 A on up to 92 circuits (84 branch circuits, two three-phase mains, and two neutrals). The E30 has a sampling frequency of 2560Hz, an overload capability of 22kAIC, and an input power of 90 to 277VAC, 50/60Hz. The user configurable thresholds trigger alarm indicators when any circuit approaches the threshold, preventing overload. Data updates occur every 1.8 seconds, providing you with up-to-date information vital to overload prevention. Recorded data may be easily transferred to a local PC via the Modbus RTU networked connection.

Features

  • IEC Class 1 metering accuracy
  • Up to 126 panelboards can be monitored on one RS-485 drop...simplifies wiring
  • Reports voltage, current, power and energy for mains and branches...one product covers the whole panelboard
  • Monitors up to 46 circuits (42 branch circuits, one 3-phase main, one neutral) with one device...saves space
  • 3/4" spaced solid-core 100 A current sensors…flexible installation
  • 4 user-configurable alarm threshold registers and individual monitoring of all branches...improved load management
  • Built-in ability to set the orientation and numbering of the circuits
  • 1/4 A to 100 A monitoring...widest dynamic range in the industry
  • Flexible installation options - can use ribbon cables from 18" (0.46 m to 20 ft (6 m)
  • Versatile support for any combination of 1, 2, 3 pole breakers

Applications

Ideal for the following applications: Branch Circuit Monitoring in New Construction, Load Based Cost Allocation, Overload Protection, Load Management, Load Balancing and Lighting Circuits.

Key Features

  • Revenue Grade measurements
  • IEC Class 1 metering accuracy
  • Up to 126 panelboards can be monitored on one RS-485 drop...simplifies wiring
  • Reports volts, amps, power, and energy for each circuit...one product covers the whole panelboard
  • 92 circuits with one product (84 branch circuits, 2 3-phase mains, 2 neutrals)... saves space
  • 3/4", or 1", or 18 mm spaced solid-core current sensors...flexible installation
  • Split-core version has two mounting options (DIN Rail or Snaptrack)... installation flexibility
  • 4 user-configurable alarm threshold registers...improved load management
  • Built-in ability to set the orientation and numbering of the circuits
  • 1/4 amp to 100 amp solid-core monitoring...widest dynamic range in the industry
  • 1, 2, 3 pole breaker support
  • Applications for new construction (solid-core version) and retrofits (split-core version)
  • Modbus RTU standard
  • Modbus TCP over Ethernet available with addition of U013-0012...page 166
  • BACnet IP or MS/TP available with addition of E8950...see page 164 (E30Ax84 and E31Axxx not supported)

Specifications

Inputs:
  • Input Power 90-277 VAC, 50/60 Hz
Accuracy:
  • Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
  • Voltage ±0.5% of reading 90-277 V line-to-neutral
Operation:
  • Sampling Frequency 2560 Hz
  • Update Rate 1.8 s
  • Overload Capability 22 kAIC
Network Communications:
  • Type Modbus® RTU
  • Connection DIP switch-selectable 2-wire or 4-wire, RS-485
  • Address DIP switch-selectable address 1 to 247 (pairs of 2)
  • Baud Rate DIP switch-selectable 9600, 19200, 38400
  • Parity DIP switch-selectable NONE, ODD, EVEN
  • Communication Format 8 data-bits, 1 start-bit, 1 stop-bit
Mechanical:
  • Ribbon Cable Support 2 ea 4 ft. (0.9 m) flat ribbon cables ship standard; up to 20 ft. (6 m) available
Environmental:
  • Operating Temperature 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
  • Storage Temperature -40° to 70°C (-40° to 158°F)
Safety:
  • UL508, EN61010
Click here for complete specifications on the Veris E30A042

Veris E30A042 Specifications

Input Power 90-277 VAC, 50/60 Hz
Power Energy IEC 62053-21 Class 1, ANSI C12.1-2008
Sampling Frequency 2560 Hz
Update Rate 1.8 s
Overload Capacity 22 kAIC
Click here for complete specifications on the Veris E30A042

What's included with the Veris E30A042

  • E30A042 Advanced Main Circuit Board
  • 2 x Strips of 21 ea 100 A Solid Core Current Transducers Spaced 3/4" Apart
  • 2 x 4ft Flat Ribbon Cables

Veris E30 Series Comparison

Monitoring at Mains E30A E30B E30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage, L-L and average
Voltage, L-N and average
Voltage, L-N and per phase
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under

* Based on a 3-phase breaker rotation.

Ask a question about Veris E30A042 Panelboard Monitoring System, Power and Current for One 3-Phase Main, Advanced