Analog/Digital 10kV Megger; 500, 1000, 2500, 5000, 10,000V; 20 Tohms; Cat IV 600V.
Analog/Digital 10kV Megger; 500, 1000, 2500, 5000, 10,000V; 20 Tohms; Cat IV 600V.
The Megger MIT1025 10 kV Insulation Resistance Tester meets IP65 standards and can take measurements when connected to line power/mains with a dead battery.
Features
Applications
Insulation Range, Analog | 100kW to 10TW |
Insulation Range, Digital | 10kW to 20TW |
Test Voltages | 500V, 1000V, 2500V, 5000V, and 10,000V |
User Defined Test Voltages | 100V to 1kV in 10V steps 1kV to 5kV in 25V steps 5kV to 10kV in 25V steps |
Accuracy | ±5% to 2TΩ, ±20% to 20TΩ |
Voltage Output Accuracy | +4% -0% ±10V of nominal test voltage at 1GW load |
Voltmeter Range | 30 to 660V AC/DC, 50/60Hz |
Voltmeter Accuracy | ±3% ±3V |
Frequency Range | 45 to 65Hz |
Short Circuit Current | 3mA nominal, max. power on all loads outperforming many 5mA testers |
Insulation Alarm | 100kΩ to 1GΩ |
Current Range | 0.01nA to 6mA |
Current Accuracy | ±5% ±0.2 nA at all voltages |
Capacitance Range (above 500V) | 10nF to 25µF (dependent on measurement voltage) |
Capacitance Accuracy | ±10% ±5nF |
Capacitor Charge | <5s per µF at 3mA to 10kV |
Capacitor Discharge | <500 ms/µF to discharge from 10,000V to 50V |
Insulation Range, Analog | 100kW to 10TW |
Insulation Range, Digital | 10kW to 20TW |
Test Voltages | 500V, 1000V, 2500V, 5000V, and 10,000V |
User Defined Test Voltages | 100V to 1kV in 10V steps 1kV to 5kV in 25V steps 5kV to 10kV in 25V steps |
Accuracy | ±5% to 2TΩ, ±20% to 20TΩ |
Voltage Output Accuracy | +4% -0% ±10V of nominal test voltage at 1GW load |
Voltmeter Range | 30 to 660V AC/DC, 50/60Hz |
Voltmeter Accuracy | ±3% ±3V |
Frequency Range | 45 to 65Hz |
Short Circuit Current | 3mA nominal, max. power on all loads outperforming many 5mA testers |
Insulation Alarm | 100kΩ to 1GΩ |
Current Range | 0.01nA to 6mA |
Current Accuracy | ±5% ±0.2 nA at all voltages |
Capacitance Range (above 500V) | 10nF to 25µF (dependent on measurement voltage) |
Capacitance Accuracy | ±10% ±5nF |
Capacitor Charge | <5s per µF at 3mA to 10kV |
Capacitor Discharge | <500 ms/µF to discharge from 10,000V to 50V |