Compatible with the 5010, 5020, and 5050 loggers and 6310 and 6315 power meters, this clamp sensor provides easy and safe installations in existing facilities without errors. In addition, this leakage/load current detection type clamp sensor features a rated current of 70 A AC and fits conductors 1.6" (40 mm) in diameter.
Compatible with the 5010, 5020, and 5050 loggers and 6310 and 6315 power meters, this clamp sensor provides easy and safe installations in existing facilities without errors. In addition, this leakage/load current detection type clamp sensor features a rated current of 70 A AC and fits conductors 1.6" (40 mm) in diameter.
Rated Current | 70 A AC |
Output Voltage | 3500 mV/70 A AC (50 mV/A AC) |
Accuracy | 0 to 40 A ±1% rdg ±0.1 mV (50/60 Hz) ±2% rdg ±0.2 mV (40 Hz to 1 kHz) 40 to 70 A ±5% rdg (50/60 Hz) ±10% rdg (45 Hz to 1 kHz) |
Output | Connector: MINI DIN 6-pin Impedance: Approximately 100 Ω |
Applicable Standards | IEC 61010-1, IEC 61010-2-032 CAT III 300 V pollution degree 2, IEC 61326 |
Operating Temperature/Humidity Range | 32 to 122°F (0 to 50°C), less than 85% RH (without condensation) |
Conductor Size | Ø1.6" (Ø40 mm) |
Cable Length | Approximately 6.56' (2 m) |
Dimensions | 5 x 3.2 x 1.4" (128 x 81 x 36 mm) |
Weight | Approximately 8.5 oz (240 g) |